Wire Size Calculator

Recommend AWG wire gauge based on amperage and distance. Shows maximum ampacity for common wire gauges.

Recommended Wire Size
Voltage Drop at Recommended Size

AWG Wire Ampacity Reference (Copper, 60°C)

AWGMax AmpsTypical Use
1415ALight fixtures, 15A circuits
1220AKitchen, bathroom outlets
1030ADryers, A/C units
840ARanges, large A/C
655ASub-panels, large appliances
470AFeeder circuits
295ASub-panels, large feeders
1110AService entrance
1/0125AService entrance
2/0145A200A service
3/0165A200A service
4/0195ALarge service entrance

How to Choose Wire Size

Select the smallest AWG where: Ampacity ≥ Load AND Voltage Drop ≤ Max %

Wire sizing considers two factors: the wire must handle the current safely (ampacity) and keep voltage drop within acceptable limits for the distance.

The 80% Rule

For continuous loads (running 3+ hours), the NEC requires circuits be loaded to no more than 80% of the wire/breaker rating. A 20A circuit should carry no more than 16A continuously.

Example:
20A load, 75 ft distance, 120V, 3% max drop:
14 AWG: drop = 7.57V (6.3%) ❌
12 AWG: drop = 4.76V (4.0%) ❌
10 AWG: drop = 3.00V (2.5%) ✓
Recommendation: 10 AWG

FAQ

What is AWG?

American Wire Gauge (AWG) is a standardized wire sizing system. Lower numbers indicate larger (thicker) wire with more current-carrying capacity and less resistance.

Should I always use the minimum recommended size?

It's good practice to go one size larger than minimum for future capacity and to account for temperature derating, conduit fill, or bundled wires.